An underlayment data sheet looks simple, but four lines decide how you should read it: the roll size, the coverage after laps, the time the product may sit in the sun, and the warranty name. In Florida the third line matters most. A reroof can sit with only underlayment on it for days or weeks while a permit inspection, a material delivery or a storm delays the next step, and each product has its own limit for that wait. This article uses Owens Corning sheets (viewed 2026-11-04) to show how to read these lines. AV Construction Group works with Owens Corning products, and the manufacturer is one of its material suppliers. The figures are the manufacturer's published data, not a promise of how a roof will perform in a storm. For the code's methods and the secondary water barrier, read our article on the secondary water barrier.
Roll size and net coverage
A roll's size is printed as length and width, and the sheet also lists a coverage figure. The two differ, and the difference is the laps.
- DeckDefense: 250 ft by 48 in is 1,000 square feet gross. The sheet lists 937 square feet with a 3-inch lap, because with that lap only 45 of every 48 inches of width add new coverage.
- ProArmor: 286 ft by 42 in is about 1,001 square feet gross, and the sheet lists 929 square feet. That is consistent with a lap of about 3 inches.
- WeatherLock Mat lists 200 square feet gross for a 66.7 ft by 3 ft roll, so laps still come out of that number.
The lesson is arithmetic. A quote that counts rolls from the gross size will run short, and one that counts from the net coverage will not. Ask how many squares of underlayment the proposal assumes, and whether the count uses the net figure. If a quote lists a number of rolls, multiply it by the net coverage per roll and compare the result with the measured roof area plus the waste the contractor allows.
UV exposure time
Synthetic and self-adhered sheets are not meant to stay uncovered forever. Each sheet lists how long the product may be exposed to sunlight before the roof covering goes on. The listed times in these examples:
- ProArmor and RhinoRoof U20: up to 90 days.
- DeckDefense and the Titanium UDL series: up to 6 months.
- WeatherLock Specialty Tile and Metal: up to 180 days.
These are the manufacturer's listed limits for each product, and they count calendar time in the sun, not working days. They also assume the product was installed as the sheet requires. A two-month delay uses up most of a 90-day window, and Florida has a long rainy and storm season, so ask the roofer for the planned schedule and what happens if it slips. For storm-damaged roofs, temporary repairs after a storm explains what protects a roof in the meantime.
What the table looks like
| Product | Type | Roll and net coverage | UV exposure listed | Warranty named on the sheet |
|---|---|---|---|---|
| DeckDefense | Synthetic | 10 squares, 250 ft x 48 in, 937 sq ft with 3-inch lap | Up to 6 months | 30-year limited |
| ProArmor | Synthetic, under asphalt shingles and metal | 10 squares, 286 ft x 42 in, 929 sq ft | Up to 90 days | 10-year limited |
| RhinoRoof U20 | Synthetic | See sheet | Up to 90 days | 20-year limited |
| Titanium UDL25, UDL30, UDL50 | Premium synthetic | See sheet | Up to 6 months | See sheet |
| WeatherLock Mat | Self-sealing ice and water barrier | 2 squares, 66.7 ft x 3 ft, 200 sq ft gross | See sheet | 5-year |
| WeatherLock Specialty Tile and Metal | Self-adhered, under tile and metal | 2.14 squares, 71.3 ft x 3 ft, 214 sq ft | Up to 180 days | 30-year |
| Titanium PSU30 | Self-adhered, high temperature | See sheet | See sheet | See sheet |
WeatherLock Specialty Tile and Metal lists resistance to temperatures up to 260 degrees F, and Titanium PSU30 lists a minimum slope of 2:12. Each sheet lists its own limits, and none of them describes how a product performs beyond those limits.
Synthetic versus self-adhered
A synthetic underlayment is a woven or coated sheet nailed to the deck, and it is mechanically fastened. A self-adhered one is a peel-and-stick membrane that bonds to the deck. The data sheets show the practical difference. The synthetic rolls are large and cover about 930 square feet. The self-adhered rolls are much smaller, at around 200 square feet. The Florida Building Code names ASTM D1970 for self-adhering polymer-modified bitumen underlayment, and ASTM D226 Type II, D4869 Type III or IV and D8257 for the two-layer mechanically fastened method.
The Florida Building Code, Residential, 8th Edition (2023), lists ASTM D226, D1970, D4869, D6757 and D8257 in Section R905.1.1, and says underlayment made to those standards must bear a label with the standard and, when it applies, the type. In the High-Velocity Hurricane Zone, Miami-Dade's summary of its 2023 roofing changes says underlayment is installed to the roofing component's product approval and carries the same labels. So the roll in the truck should have a label that matches the approval in your permit file.
The warranty line
A line such as "30-year limited" is a name, not a description. It tells you which document to find. It does not say what the warranty covers, what it excludes, who may install the product or how the roof must be finished. Read the real warranty from the manufacturer for the product and the roof system in your contract, and keep a copy with your permit papers. This is the same point as in how long roofs last: a warranty term is not a lifespan.
Questions people ask
Which is better for Florida, synthetic or self-adhered?
Neither is better in general. The right choice depends on the roof covering, the slope, the approval in your permit and the building department's rules, so ask your roofer why the proposed product fits your roof.
How long can underlayment stay uncovered?
Only as long as the data sheet for that exact product allows, and the sheet counts calendar days in the sun. Ask for the planned schedule in writing.
Does a longer UV time mean a stronger roof?
No. It means the underlayment tolerates sun longer before the roof covering goes on. It says nothing about wind or water performance after that.
Do I need the same brand for the shingles and the underlayment?
Not necessarily, but they must suit each other. The Florida evaluation report for Owens Corning shingles says the underlayment must be acceptable to the shingle manufacturer and hold a current Florida Product Approval or a local approval. Ask your roofer to show the approval or data sheet that covers the full system.
Check before you decide
- Ask for the product name and the data sheet, and compare gross and net coverage.
- Ask how many squares the quote counts and whether laps are included.
- Ask for the product's UV exposure time and the planned schedule.
- Check that the roll carries a label with the standard it meets.
- Confirm the approval or listing that covers the underlayment in your permit.
- Read the real warranty document for the product.
- Ask your roofing contractor what happens if rain or a delay extends the exposure.
AV Construction Group works with Owens Corning products and counts the manufacturer among its material suppliers. If you would like a roof quoted with these materials, you can request a roofing estimate from AV, read about our roofing services or contact us.
The figures come from published manufacturer data sheets and public approvals. This article is general information, not engineering advice, and codes and approvals change, so verify details with your building department.