SEER2, EER2 and HSPF2 ratings for Florida AC replacement

What SEER2, EER2 and HSPF2 mean, what DOE changed in 2023, and which minimums apply when you replace central AC or a heat pump in Florida.

By AV Construction Group Corp. Published 5 min read

Illustration for articles about HVAC

SEER2 measures how efficiently a central air conditioner or heat pump cools over a whole season. EER2 measures cooling efficiency at a single hot-day condition, and HSPF2 measures a heat pump's heating efficiency. Since January 1, 2023, these "2" ratings replaced SEER, EER and HSPF, and they are not directly comparable to the old numbers. In Florida, which DOE places in its Southeast region, a split-system air conditioner under 45,000 Btu/h must be installed at 14.3 SEER2 or higher.

What each rating means

  • SEER2 (Seasonal Energy Efficiency Ratio 2). DOE describes SEER as the heat removed from the home over the cooling season divided by the electricity used in that season. Higher is more efficient.
  • EER2 (Energy Efficiency Ratio 2). The ratio of cooling capacity in Btu per hour to power input in watts at 95°F outdoors, a measure of efficiency under peak load.
  • HSPF2 (Heating Seasonal Performance Factor 2). The heating-season equivalent for heat pumps. It matters less in Miami than in colder states, but it is still part of a heat pump's rating.

The "2" means the rating comes from the revised DOE test procedure required as of January 1, 2023.

What changed in 2023

DOE's updated test procedure (Appendix M1) raises the external static pressure used in testing, to better reflect the resistance real duct systems create. AHRI says the pressure rises "by up to five times." Because of this, the same equipment gets a lower number under the new test than under the old one.

DOE says SEER2, HSPF2 and EER2 are not directly comparable to SEER, HSPF and EER, and that compliance is based on each model's measured value. Do not subtract a fixed amount from an older rating to guess the new one. AHRI cites the U.S. Energy Information Administration as saying the standards rose by about 1 SEER from pre-2023 levels, and says minimally compliant products under the new procedure are about 7 percent more efficient.

For context, an ACHR News report from 2015 gives the earlier Southeast minimum for split-system air conditioners as 14 SEER, which took effect that year.

Minimums that apply in Florida

DOE's regional guidance lists Florida in the Southeast region. Under 10 CFR 430.32, which DOE's FAQ cites as the source, the standards are:

EquipmentMinimum
Split-system AC, under 45,000 Btu/h (Southeast)14.3 SEER2
Split-system AC, 45,000 Btu/h and above (Southeast)13.8 SEER2
Single-package AC (national)13.4 SEER2
Split-system heat pump (national)14.3 SEER2 and 7.5 HSPF2
Single-package heat pump (national)13.4 SEER2 and 6.7 HSPF2

The Southwest has its own EER2 requirements. DOE's FAQ lists no regional EER2 minimum for the Southeast. The eCFR text confirms the regional air conditioner values above for units installed on or after January 1, 2023.

Equipment types like small-duct high-velocity systems and space-constrained units have their own, lower minimums. A ductless mini-split is covered by these rules too. See mini-split vs. central AC in Florida.

Installation date vs. manufacture date

For Southeast split-system air conditioners, what counts is the installation date, not the manufacture date. DOE defines installation as connecting the refrigerant lines or electrical systems to make the unit operational. The FAQ states there are no delays or special exemptions. Heat pumps, which fall under the national standard, are tied to the date of manufacture.

DOE says it is illegal for a contractor to install a noncompliant unit in the Southeast. Suspected illegal installations can be reported to DOE. The FAQ gives an email address and phone number for that purpose.

Replacing part of a system

  • New outdoor unit with an existing indoor coil. DOE says a replacement outdoor unit made in 2023 and paired with an indoor unit made before 2023 is compliant in the Southeast only if the outdoor unit is certified as having no match and meets the regional standard.
  • Discontinued pre-2023 systems. One certified under the old test can be installed in the Southeast if it meets that region's standard. One that was never certified as a combination is not compliant for installation.
  • Existing equipment. The standards apply to equipment being installed, not to systems already in your home.

For this reason, ask for the AHRI certificate for the exact outdoor unit, indoor coil and air handler combination. Municipal A/C replacement forms commonly ask for SEER and EER values and an AHRI reference number. The City of Hialeah's form is one example.

What a higher rating does and doesn't tell you

A higher SEER2 number means less electricity per unit of cooling under test conditions. It does not account for how well the system is sized, whether the ducts leak, or how it controls humidity. See sizing and choosing an AC system in South Florida and duct leakage and testing.

Questions people ask

Is 14.3 SEER2 the same as 14 SEER?

No. They come from different test procedures and DOE says the ratings are not directly comparable. 14.3 SEER2 is the Southeast minimum for split-system air conditioners under 45,000 Btu/h installed in 2023 or later.

Do I have to replace my old AC?

No. DOE's standards apply to equipment being installed. Whether to repair or replace is a separate decision; see AC repair or replacement in Miami.

Can my contractor install a leftover 14 SEER unit?

Only if it is certified for the Southeast under the rules above. Ask for the AHRI certificate showing the SEER2 and EER2 for your exact combination.

Do ratings guarantee my savings?

No. Savings depend on your use, your home and your installation. This article makes no estimate of savings. Ask a contractor to show the assumptions behind any figure.

Check before you decide

  • Ask for the AHRI certificate for the exact combination.
  • Confirm the rating shown is SEER2 and EER2, not the older SEER.
  • Ask how the system will be sized, tested for airflow and charged.
  • Ask whether the permit includes the applicable energy forms.
  • Confirm current rules with DOE or your building department, since federal standards and local codes can change.

For equipment selection and permitting, see HVAC services.

Sources

  1. U.S. DOE: 2023 Central Air Conditioner and Heat Pump Standards FAQ
  2. U.S. DOE: Central Air Conditioner Regional Standards Guidance
  3. 10 CFR 430.32: Energy and water conservation standards (eCFR)
  4. AHRI: 2023 Energy Efficiency Standards
  5. ACHR News: Regional Standards Now in Effect, DOE Works on Enforcement (April 2015)
  6. City of Hialeah: AC Replacement Data form